Roof pitch calculator
Enter a rise and a run and this works out the pitch in degrees, the ratio, the percentage fall and the true rafter length. It then tells you which roof coverings that pitch is normally steep enough for. Work the other way if you already know the angle and need the rise.
The answer nobody gives you: there is no legal minimum roof pitch
Search for a minimum roof pitch and you will find tables presented as though they were building regulations. They are not. No Approved Document sets a minimum pitch for a roof covering. Part A covers structure. Part C requires a roof to resist moisture from the weather, and its guidance applies to roofs of any pitch, but it sets no minimum. Part L covers energy. None of them contains the number people are looking for.
What actually governs is BS 5534, the British Standard code of practice for slating and tiling, together with the fixing instructions for the specific product on the roof. That matters more than it sounds, because the minimum moves with the product and the site. A tile rated to 17.5 degrees in a sheltered location may need a steeper pitch, a longer headlap or a different underlay once exposure is taken into account. Two roofs with the same tile can have different minimums.
Pitch, ratio and fall are three names for the same thing
British roofing usually talks in degrees, flat roofing talks in falls expressed as a ratio, and imported product data often uses a percentage. They describe one measurement. A 1 in 80 fall, the minimum finished fall for a flat roof, is 0.72 degrees and 1.25 per cent. A 30 degree pitch is a 1 in 1.73 ratio and 57.7 per cent. The calculator gives all three so you are not converting by hand against a product sheet that uses a different convention from your drawing.
Rafter length is not the same as run
The true length returned above is the sloping distance from wall plate to ridge, measured along the rafter. It is always longer than the run, and it is what you order timber against. It excludes the eaves overhang and it makes no allowance for the birdsmouth, the ridge board thickness or the plumb cut, so add your overhang and set out the cuts from the drawing rather than from this number alone.
Below 12.5 degrees the covering changes
The lowest tile rating in current UK product data is 12.5 degrees, for a few low pitch concrete interlocking tiles laid at a 100mm headlap, such as Marley Mendip 12.5 and Redland Regent. Marley gives 12.5 degrees as the bottom of the range for a tiled pitched roof. Most interlocking tiles need more, and clay interlocking tiles usually start at 15 degrees.
Below that, metal is the usual covering. Profiled metal sheet is commonly rated from about 4 degrees, or 6 degrees where it carries rooflights, and standing seam systems from about 3 degrees, with some aluminium systems lower still. These are product figures, so check the system you are pricing.
Under 10 degrees it is a flat roof
A flat roof is not a shallow pitched roof with a different angle. Approved Document J defines a flat roof as one with a pitch of less than 10 degrees, and BS 6229, the code of practice for flat roof membranes, covers pitches up to 10 degrees. The covering becomes a continuous waterproof layer rather than a set of overlapping units, and the detailing at upstands, outlets and abutments changes completely. If the pitch you have calculated is in single figures, price a flat roof build-up or a metal system rated for that pitch, rather than looking for a tile that will tolerate it.
BS 6229:2025, which replaced the 2018 edition from 31 December 2025, dropped the old rule of designing at 1 in 40 to be sure of a finished 1 in 80. The finished fall still has to be at least 1 in 80. Industry guidance on the new edition treats a 1 in 60 design fall as an appropriate starting point in many cases, and generally for roofs under 50 square metres, with 1 in 40 kept for decks that deflect more than 17mm over a metre. A cross laminated timber deck needs a finished fall of at least 1 in 40, and a zero fall roof is only for a third party certified system.
From the pitch to the priced job
Built Simple takes your take-off through to an estimate you can send, then runs the schedule and the crew from the same job. Free to start.
Start free with Built SimpleFrequently Asked Questions
Is there a minimum roof pitch in the building regulations? No. No Approved Document specifies a minimum roof pitch. The limits come from BS 5534 and from the manufacturer of the particular tile, slate or sheet, and they vary with headlap, underlay and how exposed the site is.
What is the most common roof pitch in the UK? Most British pitched roofs sit between 30 and 45 degrees. That range suits plain tiles and slates, sheds water well in a wet climate, and gives usable space in the roof. It is a convention rather than a rule.
How do I convert a roof pitch to a ratio? Divide the run by the rise. A 3000mm run with a 1500mm rise is 1 in 2, which is 26.6 degrees. The calculator above shows the angle, the ratio and the percentage together.
What pitch do I need for concrete interlocking tiles? Most smooth concrete interlocking tiles laid at a 100mm headlap are rated between 12.5 and 25 degrees, and 17.5 degrees is a common figure. At a 75mm headlap, or in a granular finish, the range moves up to about 17.5 to 30 degrees. The real minimum is on the manufacturer datasheet for the specific tile, and it changes with headlap and exposure.
What is the minimum fall for a flat roof? BS 6229:2025 sets a minimum finished fall of 1 in 80, about 0.7 degrees. Design falls are steeper to allow for deflection and building tolerances: 1 in 60 is a common starting point under the 2025 edition, and 1 in 40 where the deck deflects more. The building regulations do not set the figure.
What is the lowest pitch for a tiled roof? 12.5 degrees, and only for a few low pitch concrete interlocking tiles laid at a 100mm headlap. Most tiles need 15 degrees or more, and plain tiles around 35. Below 12.5 degrees the usual answer is metal, and below 10 degrees a flat roof.
Does the rafter length include the overhang? No. The figure above is wall plate to ridge along the slope. Add your eaves overhang, and set the birdsmouth and plumb cuts out from the drawing.
Related calculators and guides
- UK stairs calculator, Approved Document K
- UK joist span and decking calculator
- Approved Documents explained
- All UK calculators
Sources
- BS 5534:2014+A2:2018, Slating and tiling for pitched roofs and vertical cladding, British Standards Institution. Paid standard, referenced rather than reproduced.
- BS 6229:2025, Flat roofs with continuously supported flexible waterproof coverings, code of practice, British Standards Institution, in effect from 31 December 2025 and replacing the 2018 edition. Paid standard. The fall figures above are as reported by the Liquid Roofing and Waterproofing Association, Bauder and the National Federation of Roofing Contractors.
- Approved Document J, Combustion appliances and fuel storage systems, 2010 edition, HM Government, for its definition of a flat roof as one pitched at less than 10 degrees.
- Approved Documents, HM Government, checked for any stated minimum pitch. There is none. Approved Document C paragraph 6.11 applies its guidance to roofs of any pitch.
- Manufacturer data checked in October 2026: Marley Mendip 12.5 and Redland Regent at 12.5 degrees with a 100mm headlap, Sandtoft 20/20 at 15 degrees with a 100mm headlap, Steadmans AS13/3 at 4 degrees or 6 degrees with rooflights, VMZinc standing seam at 3 degrees and Kalzip at 1.5 degrees.